which could be a pretty big obstacle to grid-scale deployment.
Well, on a grid scale if you’ve got a 100MWh battery and you want to charge it at 3C, then you’re looking to find a spare 300MW out on the grid somewhere for 20 minutes.
That’s not impossible, but you’ll buy that 100MWh a lot cheaper if you’re willing to get it over the course of a few hours. For example, buying power in the middle of the day when there’s excess solar, to then drop it back into the grid in a one hour burst during peak times in the evening for 10 times the price.
That kind of thing is where the battery will make the most profit, so slow charge rates don’t really matter.
Well, on a grid scale if you’ve got a 100MWh battery and you want to charge it at 3C, then you’re looking to find a spare 300MW out on the grid somewhere for 20 minutes.
That’s not impossible, but you’ll buy that 100MWh a lot cheaper if you’re willing to get it over the course of a few hours. For example, buying power in the middle of the day when there’s excess solar, to then drop it back into the grid in a one hour burst during peak times in the evening for 10 times the price.
That kind of thing is where the battery will make the most profit, so slow charge rates don’t really matter.
i think the big issue is asymmetry. they charge at 3C, but they discharge at 8C. so you need the significantly overbuild.